TESCO’s L3000® I/O configurations are customizable to meet your needs now and in the future.
Mixed I/O Modules
TESCO Mixed I/O modules have one of each type of I/O. These cards are efficient for smaller applications, since only one I/O card is required, rather than one of each type. These cards also allow the use of the compact L3000e packaging on a PLC with all types of I/O.
High Density Dedicated I/O Modules
TESCO Dedicated I/O modules allow the greatest flexibility for systems with higher I/O demands. They are the perfect solution for systems with a high demand I/O. Dedicated I/O modules may be combined with mixed I/O modules for the utmost flexibility on systems with medium to extremely large I/O demands.
Two Levels of Protection Available
- Class A
- 2 MOVs at each AI/AO
- Fused
- Class AAA
- Full 12 stage, 1000 joule lightning protection at each AI/AO
- Fuses
- MOVs
- TVS diodes
- Dual spark gaps
- Inductors
I/O Card Options
I/O Adapter | Analog Inputs | Analog Outputs | Digital Inputs | Digital Outputs | Options |
---|---|---|---|---|---|
HDIO | 6 | 2 | 16 | 8 | |
HDAI | 16 | Class A or AAA lightning protection options | |||
HDAO | 8 | Class A or AAA lightning protection options | |||
HDDI | 32 | AC or DC inputs available | |||
HDDO | 32 | 10 Amp Dual Contact Relay outputs |
I/O Specifications
Analog Input | Analog Output | Digital Input | Digital Output | |
---|---|---|---|---|
Resolution | 12-bit | 12-bit | ||
Type | Differential or Single Ended | Differential or Single Ended | Opto-Isolated | Dry Contact, Double Break 20A, Socketed |
Type | Differential or Single Ended | Differential or Single Ended | Opto-Isolated | Dry Contact, Double Break 20A, Socketed |
Modes | Current or Voltage | Current or Voltage | ||
Voltage Range | (Voltage Mode) 0 to 5V | |||
Current Range | (Current Mode) 4 to 20mA | (Current Mode) 4 to 20mA | ||
Accuracy | ± 1 LSB | ± 1/2 LSB | ||
Linearity | ± 1 LSB | ± 1 LSB | ||
Impedance | > 4MΩ in voltage mode | > 120Ω | ||
Common Mode Voltage | 96V | 96V | ||
Internal Sample Rate | 10µ | |||
Protection | MOVs, Transorb, Fuse, Spark Gap | MOVs, Transorb, Fuse | ||
Maximum Loop Impedance | (Current Mode)1kΩ | |||
Output Capacitance | .001µf | |||
Isolation Voltage | 7500V | |||
Input Sense | Dry Contact on DC inputs 120 VAC on AC inputs | |||
Operate/Release Time | 20µs Maximum | |||
Frequency Response | 1/2Hz |
Digital Output | |||||||
---|---|---|---|---|---|---|---|
Current Ratings |
|
||||||
Power Rating |
|
||||||
Life Expectancy |
|
TESCO® L3000e® Terminal Blocks
TESCO L3000e terminal blocks provide excellent lightning/surge protection and alleviate the need to install discrete interposing devices on the enclosure back-pan.
Features
- Pull-apart two piece wiring blocks for fast and easy wiring/re-wiring
- Separate wiring blocks for each I/O type with wire points fully labeled
- Versatile internal or external analog power source
- Digital outputs have socketed 10A relays with “ON” LED
- Entire terminal block snaps on/off standard track mount
- Onboard passive circuit protection to protect programmable controller
- Available with a built-in isolated 24V current loop power supply
- Individually fused AI/AO power source
- Fused DI source and common with clamping diodes
- Onboard spare fuses for all fuse types
High Density I/O Terminal Block Specifications
Loop Power Supply | DC-DC Converter. Will drive AIs and AOs. Nominal Output Voltage 24 VDC Max Output Current 161 mA |
Wire Size | 22 to 12 gauge (copper only) |
External Power Voltage Ranges | Analog loop 24 – 96 VDC Digital Input 12 VDC |
Fuse Ratings | Individual AI/AO 1/4A DI source/common 2A |
Terminal Block Dimensions
Terminal Block | Dimensions |
---|---|
High Density I/O | |
High Density Analog Input | |
High Density Analog Output | |
High Density Digital Input This terminal block has 16 inputs therefore two of these terminal blocks are required for each HDDI card. |
|
High Density Digital Output This terminal block has 16 outputs therefore two of these terminal blocks are required for each HDD0 card. |